GCK低(di)壓(ya)抽出式開關柜廣泛應用(yong)于(yu)發電(dian)(dian)(dian)(dian)(dian)廠(chang),變(bian)電(dian)(dian)(dian)(dian)(dian)所,廠(chang)礦企業和(he)高層建筑的(de)動力配(pei)(pei)電(dian)(dian)(dian)(dian)(dian)PC和(he)電(dian)(dian)(dian)(dian)(dian)動機(ji)控(kong)制(zhi)MCC,作為交流50-60Hz,額定工作電(dian)(dian)(dian)(dian)(dian)壓(ya)為660V及以下(xia),額定電(dian)(dian)(dian)(dian)(dian)流為4000A及以下(xia)的(de)發、供電(dian)(dian)(dian)(dian)(dian)系統中配(pei)(pei)電(dian)(dian)(dian)(dian)(dian)、電(dian)(dian)(dian)(dian)(dian)動機(ji)集中控(kong)制(zhi),無功補償使(shi)用(yong)的(de)低(di)壓(ya)成套配(pei)(pei)電(dian)(dian)(dian)(dian)(dian)裝置(zhi)。
產品使用環境(jing)
額定絕(jue)緣電(dian)壓:交流660V,交流1000V
額定工作(zuo)電壓:交流(liu) 380 V ,交流(liu)660 V
額定頻率:50Hz
饋電電路(lu)大電流:3150A
抽屜回路大電流:3150A
控制電(dian)機大容量:320KW
水平母線峰值耐(nai)受電流(0.1S):63KA、105KA、176KA
水(shui)平母(mu)線短時耐受電流(liu)(1S):30 KA、50 KA、80 KA、100 KA
垂直母線峰值耐受電流(0.1S):63 KA、105 KA
垂直母線(xian)短時耐受電(dian)流(1S):30 KA、50 KA
額定工頻耐受電(dian)壓(1min):2500V
二次(ci)工頻耐受電壓(ya)(1min):2500V
防護等級(ji):IP30、IP40
外型(xing)尺(chi)寸寬*深*高mm:600(800、1000)*800(1000)*2200
產(chan)品(pin)使用環境
1、周圍空氣(qi)溫(wen)度不高(gao)于(yu)(yu)+40℃,不低(di)于(yu)(yu)-5℃,24h內的平(ping)均溫(wen)度不得(de)高(gao)于(yu)(yu)+35℃,超過時,需根據實際情況降容運(yun)行;
2、戶內使用(yong):使用(yong)地點的海拔不得超過(guo)2000m
3、周圍空氣相對(dui)溫(wen)度為(wei)+40℃時(shi)不超(chao)過(guo)百分(fen)之50,在較低溫(wen)度時(shi)允許(xu)有(you)較大的相對(dui)溫(wen)度,如+20℃時(shi)為(wei)百分(fen)之90,應考慮到由(you)于溫(wen)度的變化可能會(hui)偶然產生凝露的影響;
4、裝置(zhi)安(an)裝時與垂直面(mian)的斜度不超過5℃,且整(zheng)組柜列(lie)相對平(ping)整(zheng)(符合GBJ232-82標準(zhun));
5、裝置應(ying)安裝在無劇烈(lie)震動和沖擊以及(ji)不(bu)足以使電器元(yuan)件受(shou)到不(bu)應(ying)有(you)腐蝕的場所;
6、用(yong)戶有(you)特殊要求可以與制造廠協商解(jie)決
電 話(hua):0515-88449499
手 機:181-5139-5999 徐(xu)經理
181-5139-2223 王經理
152-9530-5677 凌經理
181-5138-5557 張經理
181-1429-5559 彭(peng)經理
153-5172-8458 徐經理
地 址:江(jiang)蘇省鹽(yan)城市新都(dou)西路(lu)189號神龍公路(lu)港(gang)
![]() | ![]() |
官方微信 | 手機網站 |